BOLZTHERM® AW-50 is ideally suited for heating and cooling applications due to its unique composition. It is approved for use in closed, non-pressurized heat transfer systems with forced circulation within a temperature range of -56 °C to 260 °C, ensuring that the maximum film temperature of 285 °C is not exceeded. The optimal operating range is between 30 °C and 250 °C. For applications outside this range, please contact us for further consultation.
Typical characteristics | Unit | Standard | Value |
---|---|---|---|
Area of application | [°C] | - | -56 bis 260 |
Max. flow temperature | [°C] | - | 260 |
Max. film temperature | [°C] | - | 285 |
Viscosity at 40 °C | [mm²/s] | DIN 51562-1 | 4,04 |
Viscosity at 100 °C | [mm²/s] | DIN 51562-1 | 1,63 |
Density at 20 °C | [kg/m³] | DIN 51757 | 857 |
Pourpoint | [°C] | DIN ISO 3016 | -80 |
Flash point | [°C] | DIN EN ISO 2719 | 140 |
Flash point | [°C] | DIN EN ISO 2592 | 145 |
Acid value | [mg KOH/g] | DIN ISO 6618 | ≤ 0,2 |
Coke residue | [w.-%] | DIN EN ISO 10370 | < 0,1 |
Boiling point at 1013 mbar | [°C] | - | 293 |